| Įtampa | 12 to 30 Vdc normal |
| Tiekimo srovė | 5.5mA in all operational states |
| Temperatūra | -10°C to +55°C |
| Drėgmė | 10 to 95% RH Non-condensing |
| Apsauga | IP65 when suitably mounted and terminated |
| Optinis bangos ilgis | 870nm |
| Maksimalus kampinis išlyginimas | ±5° |
| Didžiausias kampinis poslinkis | (static not auto-aligning) |
| Signalizacijos jautrumo lygiai | 25% (1.25dB) to 50% (3dB) in 1% (0.05dB) increments (default 35% (1.87dB)) |
| Signalizacija | Obscuration drops to below pre-defined sensitivity level. Time to Alarm Condition adjustable between 2 to 30 seconds in 1 second increments (default 10 seconds) |
| Signalizacijos indikacija | App Status – FIRE, Head Red Flashing LED, Alarm Relay Change Over (CO) Contact, Rating 2A @ 30 VDC |
| Test / Reset funkcijos | Beam test function with App, Alarm latching / auto-reset selectable (default auto-reset), Alarm reset in latching mode with App reset function, removing power for >5 seconds or momentarily apply >5 VDC to reset connections in Beam Head |
| Gedimų jautrumo lygis | <4% |
| Gedimai | Obscuration drops to below the fault sensitivity level within 1 second, Power Down or Supply Voltage < 9 VDC, Commissioning modes, Pre-Alignment and Auto-Alignment, Beam turned off during Beam Maintenance, Time to Fault Condition adjustable, 2 to 60 seconds in 1 second increments (default 10 seconds) |
| Gedimo indikacija | App Status – FAULT, Head Yellow Flashing LED 1 Second, Fault Relay Change Over (CO) Contact Rating 2A @ 30 VDC |
| Normali Būklė | Obscuration level is above the Alarm sensitivity level, App Status – NORMAL, Programmable on/off, Head Green Flashing LED, Programmable on/off |
| Automatinis išlygiavimas / kompensavimas | Auto-align during normal operation if obscuration drops below 90% for the duration of the align time set (doesn’t affect normal operating mode), Beam Contamination Compensation 4 hour monitoring. Compensation data available in the App |